• Monitoring of phase sequence and phase failure
• Monitoring of asymmetry
• Connection of neutral wire optional
• Supply voltage = measuring voltage
Meassuring circuit data |
|
Functions |
monitoring of phase sequence, phase failure and asymmetry |
with adjustable asymmetrie, connection of neutral wire optional |
|
LED indicator |
yellow LED, green LED |
Measuring circuit |
|
• terminals |
(N)-L1-L2-L3 |
• measuring variable |
3N-, sinus, 48…63 Hz |
• measuring input |
= supply voltage 3(N)~ 400/230 V |
• overload capacity |
determined by tolerance specified for supply voltage |
• asymmetry |
5…25% |
Input circuit |
|
Rated voltage U |
3(N)~ 400/230 V |
Rated power consumption |
8,0 VA / 0,8 W |
Rated frequency |
AC: 48...63 Hz |
Output circuit |
|
Number and type of contacts |
1 C/O - changeover |
Rated load AC1 |
5 A / 250 V AC |
Max. breaking capacity AC1 |
1 250 VA |
Insulation |
|
Rated surge voltage |
4 000 V AC |
Overvoltage category |
III PN-EN 60664-1 |
Insulation pollution degree |
2, if built-in 3 PN-EN 60664-1 |
Monitoring relay, Contacts:1C/O, Voltage monitoring in 3-phase mains